Testboy TV 455VDE-tester Testboy TV 455 Manuale Utente

Codici prodotto
Testboy TV 455
Pagina di 76
TESTBOY TV 450 
PE test terminal 
 
50 
PE terminal test procedure 
 
‰
 
Connect test cable to the instrument. 
‰
 
Connect test leads to the to the item to be tested (see 
figures 5.33 and 5.34). 
‰
 
Touch PE test probe (the TEST key) for at least one second. 
‰
 
If PE terminal is connected to phase voltage the warning message is displayed, 
instrument buzzer is activated, and further measurements are disabled in Z-
LOOP and RCD functions. 
 
Warning:
 
‰
 
If dangerous voltage is detected on the tested PE terminal, immediately stop all 
measurements, find and remove the fault! 
 
Notes:
 
‰
 
In the SETTINGS and VOLTAGE TRMS menus the PE terminal is not tested. 
‰
 
PE test terminal does not operate in case the operator’s body is completely 
insulated from floor or walls!