Battery fuse: Use a fast acting fuse with a minimum interrupt rating of 1000 A on the battery side. We  
recommend to use a fast acting melting fuse (e. g. car type fuses) as close as possible to the battery  
terminal. The maximum current rating should be 1.5 times of the nominal current of the charge  
controller.
Please do not disassemble or attempt to repair Phocos products. Phocos charge controllers do not 
contain user serviceable parts.
Please observe all instructions with regards to external fuses/breakers as indicated.
Maintenance and installation notes 
When installing or working on the PV system, please disconnect the PV (solar) modules from the 
charge controller first, to prevent any damages to the charge controller!
Please verify that all cable/wire connections are tightly fastened to the connectors/binding posts in 
order to avoid any bad or loose connections that could result in excessive heating.
Please install a fuse or breaker near the battery before installing or adjusting the controller!
Please install and operate the controller in a dry environment.
High voltage risks
Operation of this device may produce high voltages which can cause severe injuries or death in case 
of improper installation or operation of the device.
PV modules can generate high DC voltages!
Make sure the cables are always connected to the correct terminal. An electrical shock can be lethal. 
In general, any electric shock can be dangerous to your health. 