Commisioning 
Dezember 06 
 
13
 
3.2 
Independent Actions 
3.2.1  Monitoring of Values by Polling the PA Buffer 
The LOGO! PA buffer values are monitored in order to generate a fault message 
when a value changes. 
This monitoring is performed in the polling operation, that is, the INSYS GSM 4.2 
LOGO! reads out the LOGO! PA buffer cyclically, thus enabling changes to be 
detected. 
The scan interval can be set in the seconds range (1 to 255 s).  
If a change in a monitored value is registered, a fault message is transmitted 
(SMS, SMS to fax, SMS to e-mail, SMS to conventional telephone). 
In the case of digital values, the following events (selectable) can trigger 
transmittal of a fault message: 
-  Change to 0 
-  Change to 1 
-  Any change  
 
For analog values, an upper limit and a lower limit must be specified; in this case, 
the following events (selectable) can also trigger transmittal of a fault message: 
-  Value leaves the specified range (lower limit to upper limit) 
-  Value enters the specified range (lower limit to upper limit) 
-  Any range change 
 
The fault message can have the following content (selectable): 
-  PA-SMS: An image of the PA buffer (utilized values) containing all current 
values at the time of the change is received. Depending on the number of 
utilized values in the PA buffer, the SMS can also be divided into multiple (up 
to 3) SMS. This message cannot be sent as an e-mail. 
-  Text message with predefined message: This facilitates easier classification of 
the change. A general message can be prefixed to each of these messages (e.g., 
with asset number, address, etc.).