Bender VMD4105-D-2 B93010045 Scheda Tecnica
Codici prodotto
B93010045
Function
17
3.2.6
Delay times
t
on
and
t
off
Delay time for connection
t
on
When all voltage and frequency values measured, meet the conditions for
connection during the delay time for connection, the alarm LEDs will go out
and the alarm relays will switch.
connection during the delay time for connection, the alarm LEDs will go out
and the alarm relays will switch.
Response delay
t
off
Minimum period for an error to exist until the alarm relays will switch.
3.2.7
Password protection
By default, the password protection is deactivated (off).
3.2.8
Factory setting
After activating the factory setting, all previously changed settings are reset to
delivery status.
delivery status.
3.2.9
Erasable history memory
The device utilises a history memory for failsafe storing of up to 300 data
records (date, time, channel, event code, measured value).
records (date, time, channel, event code, measured value).
23
Both LEDs
flash
flash
Internal error
Make a note from the error
code "xx“ and contact the
Bender Service.
code "xx“ and contact the
Bender Service.
Remote
trip
trip
Both LEDs
light con-
tinuosly
light con-
tinuosly
Remote trip
active
active
Activate RTG/RT1 or deacti-
vate the input via the menu
(off )
vate the input via the menu
(off )
Enter
norm
norm
Both LEDs
light con-
tinuosly
light con-
tinuosly
No norm
selected
selected
Select the application norm
from the menu.
from the menu.
Code/
Message
Message
LED
Meaning
Remedy