Procedure:
1. Open the housing of the SECU-DATA 1232. Avoid the intrusion of
moisture and pollution while the instrument is open to maintain the
long-term reliability
long-term reliability
2. Turn on the power supply of the SECU-DATA 1232
3. Press shortly on both instruments the A-button (need not be at the
3. Press shortly on both instruments the A-button (need not be at the
same time on both devices)
4.
The green “RF”-LED and the yellow “Power“-LED on the SECU-
DATA 1232 start blinking alternately
DATA 1232 start blinking alternately
– the instruments are in the
matching mode now
5. After completion both instruments perform automatically a RESET
– the red LED flashes shortly. If the tuning process is not success-
ful you can abort it by pressing shortly the button A
ful you can abort it by pressing shortly the button A
– the original
settings remain in memory
6. Now
the green “RF”-LED and the yellow “Power”-LED on both de-
vices are continuously on
– the matching procedure is finished suc-
cessfully and the RF-connection is established.
Monitoring the RF-status, Alarms
Depending on the application it might be important to monitor the status of
the RF-connection and to generate an alarm indication in case of interrup-
tions.
As soon as the RF-connection between two matched devices is established
the green RF-LEDs go on and the power supply voltage is connected to
terminal 8 of both instruments (the maximum load current is 500mA). If the
RF-connection is interrupted or if there is a power failure on one of the de-
vices the internal relay contact will open, terminal 8 is open then.
the RF-connection and to generate an alarm indication in case of interrup-
tions.
As soon as the RF-connection between two matched devices is established
the green RF-LEDs go on and the power supply voltage is connected to
terminal 8 of both instruments (the maximum load current is 500mA). If the
RF-connection is interrupted or if there is a power failure on one of the de-
vices the internal relay contact will open, terminal 8 is open then.