5.3 Special functions 
LOGO!Soft Comfort Online Help 
Operating Instructions, 06/2014 
261
 
Timing diagram A: Function with negative difference Delta 
 
Timing diagram B: Function with positive difference Delta 
 
Description of the function 
The function fetches the analog signal at input Ax.  
Ax is multiplied by the value of the A (gain) parameter, and the value at parameter B (offset) 
is added to product, i.e. 
(Ax * gain) + offset = actual value of Ax. 
Output Q is set or reset, depending on the set (On) threshold and difference value (Delta). 
The function automatically calculates the Off parameter: Off = On + Delta, whereby Delta 
may be positive or negative. See the calculation rule below. 
Calculation rule 
●  When you set a negative differential value Delta, the On threshold ≥ Off threshold, and: 
Q = 1, if the actual value Ax > On 
Q = 0, if the actual value Ax ≤ Off. 
See the timing diagram A. 
●  When you set a positive differential value Delta, the On threshold < the Off threshold, and 
Q = 1, if: 
On ≤ the actual value Ax < Off. 
See the timing diagram B. 
Particular characteristics to be noted when configuring 
Refer to the help on analog block parameters in the Information on analog value processing 
(Page 286) section. 