LOGO!Soft Comfort Online Help 
262
 
Operating Instructions, 06/2014 
5.3.3.3 
Analog comparator 
 
Short description 
The output is set and reset depending on the difference Ax – Ay and on two configurable 
thresholds.  
 
Connection 
Description 
Inputs Ax, Ay 
Inputs Ax, Ay are two analog signals from the followings: 
• 
AI1 to AI8 
(
*
)
 
• 
AM1 to AM6 (if 0BA6), AM1 to AM16 (if 0BA7), or AM1 to AM64 (if 0BA8) 
• 
NAI1 to NAI32 (if 0BA7 or 0BA8) 
• 
AQ1 and AQ2 (if 0BA7), or AQ1 to AQ8 (if 0BA8) 
• 
NAQ1 to NAQ16 (if 0BA7 or 0BA8) 
• 
The block number of a function with analog output 
Parameter 
Gain 
Range of values: -10.00 to 10.00 
Offset 
Range of values: -10000 to 10000 
On: On threshold 
Range of values: -20000 to 20000 
Off: Off threshold 
Range of values: -20000 to 20000 
p: Number of decimals 
Range of values: 0, 1, 2, 3 
Output Q 
Q is set or reset depending on the set thresholds. 
* AI1 to AI8: 0 to 10 V corresponds with 0 to 1000 (internal value). 
 
 
 
0BA4: 
A: Gain 
Range of values: 0.00 to 10.00 
 
0BA0-0BA3: 
The following parameters apply: 
G : Gain in [%] 
Range of values: 0% to 1000% 
O : Offset 
Range of values: -999 to 999 
delta : Threshold 
Q is set to 1 when the difference Ax-Ay exceeds the threshold.