Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 Scheda Tecnica

Codici prodotto
6ED1057-3BA00-0AA8
Pagina di 378
Reference material 
 
5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
328
 
Operating Instructions, 06/2014 
Description of the function 
With a 0 to 1 transition of the signal at input En, the display outputs your configured message 
text (actual value, text, TOD, date) in RUN mode. 
Acknowledgement disabled (Ack = Off): 
The message text is hidden with a 0 to 1 signal transition at input En. 
Acknowledgement enabled (Ack = On): 
After input En is reset to 0, the message text is displayed until acknowledged by pressing the 
OK button. The message text cannot be acknowledged as long as input En is high. 
If several message text functions were triggered with En=1, the message with the highest 
priority (0 = lowest, 30 = highest) is displayed. This also implies that a new message text is 
only displayed if its priority is higher than that of previously enabled message texts. 
After a message text is disabled or acknowledged, the function automatically shows the 
previously active message text that takes the highest priority. 
You can change between the display in RUN mode and the message texts by means of the 
 and   buttons.  
Restrictions 
Up to ten message text functions are available.