Wago 750-553 Fieldbus Independent I/O Module 750-553 Scheda Tecnica
Codici prodotto
750-553
750-553 [4 AO DC 0-20 mA]
• 7
View
WAGO-I/O-SYSTEM 750
I/O Modules
I/O Modules
2 I/O Modules
2.1 Analog Output Modules
2.1.1 750-553 [4 AO DC 0-20 mA]
4-Channel Analog Output Module 0 – 20 mA
2.1.1.1 View
A1 A2
13 14
C
D
D
B
A
M M
A3 A4
M M
750-553
AO 2
AO 1
AO 4
AO 3
0V
0V
0V
0V
Power jumper
contacts
Datacontacts
Function
Error
Fig. 2.1.1-1: View
g055300e
2.1.1.2 Description
The analog output module 750-553 creates a standardized signal of 0 – 20
mA.
mA.
The module has four output channels and enables, for example, the direct
wiring of four 2-conductor actuators to the connections AO 1 and Common
(ground) or AO 2, AO 3, AO 4 and each with Common (ground). The signals
are transmitted via AO 1, AO 2, AO 3 or AO 4.
The channels have a common ground.
wiring of four 2-conductor actuators to the connections AO 1 and Common
(ground) or AO 2, AO 3, AO 4 and each with Common (ground). The signals
are transmitted via AO 1, AO 2, AO 3 or AO 4.
The channels have a common ground.
Attention
All load impedances connected to the outputs of one I/O module have to be
either in the range of 0 ... 300
All load impedances connected to the outputs of one I/O module have to be
either in the range of 0 ... 300
Ω or 300 ... 600 Ω.
The load impedances are checked by the I/O module and inadmissible load
combinations will cause an error message.
combinations will cause an error message.
The input signal is electrically isolated and will be transmitted with a
resolution of 12 bits.