Wago 750-553 Fieldbus Independent I/O Module 750-553 Scheda Tecnica
Codici prodotto
750-553
8 •
750-553 [4 AO DC 0-20 mA]
Display
Elements
WAGO-I/O-SYSTEM
750
I/O
Modules
The operational readiness and the trouble-free internal data bus
communication of the channels are indicated via a green function LED.
communication of the channels are indicated via a green function LED.
In addition, a red error LED will show if there are any broken wire or
inadmissible load combinations.
inadmissible load combinations.
Any configuration of the output modules is possible when designing the
fieldbus node. Grouping of module types is not necessary.
fieldbus node. Grouping of module types is not necessary.
The field side supply voltage is used for the power supply of the module.
The field side supply voltage of 0 V and 24 V to downstream I/O modules is
derived from adjacent I/O modules or from a supply module. The supply
voltage for the field side is made automatically through the individual I/O
modules by means of power jumper contacts.
derived from adjacent I/O modules or from a supply module. The supply
voltage for the field side is made automatically through the individual I/O
modules by means of power jumper contacts.
Warning
The maximum current of the internal power jumper contacts is 10 A. When
configuring the system it is important not to exceed the maximum/sum
current. However, if such a case should occur, another supply module must be
added.
The maximum current of the internal power jumper contacts is 10 A. When
configuring the system it is important not to exceed the maximum/sum
current. However, if such a case should occur, another supply module must be
added.
The analog output module 750-553 can be used with all couplers/controllers
of the WAGO-I/O-SYSTEM 750 (except for the economy types 750-320, -
323,
-324 and -327).
of the WAGO-I/O-SYSTEM 750 (except for the economy types 750-320, -
323,
-324 and -327).
2.1.1.3 Display
Elements
LED Designation
State Function
off
No operational readiness or the
internal data bus communication is
interrupted
internal data bus communication is
interrupted
A
green
green
Function
on
Operational readiness and trouble-
free internal data bus
communication
free internal data bus
communication
off No
Error
13 14
C
D
D
B
A
A
B
Fig. 2.1.1-2: Display
elements
elements
g055702x
B
red
red
Error
on
Broken wire or inadmissible load
combination
combination