Tele 2390500 G2PM400VSY10 Gamma 3-Phase Voltage Monitoring Relay 3-phase voltage monitoring 2390500 Scheda Tecnica

Codici prodotto
2390500
Pagina di 4
Subject to alterations and errors
Functions
G2PM...SY10
Asymmetry monitoring
If the asymmetry of the phase-to-phase voltages exceeds the value 
set at the ASYM-regulator, the set interval of the tripping delay (DE-
LAY) begins (red LED ASYM flashes). After the interval has expired 
(red LED ASYM illuminated), the output relay switches into off-posi-
tion (yellow LED not illuminated).
If the neutral wire is connected to the device, the asymmetry of the 
phase voltages referred to the neutral wire (Y-voltage) is monitored 
also. In that case both values of the asymmetry are evaluated and if 
one of the values exceeds the value set at the ASYM-regulator, the 
set interval of the tripping delay (DELAY) begins (red LED ASYM 
flashes). After the interval has expired (red LED ASYM illuminated), 
the output relay switches into off-position (yellow LED not illuminated).
LED ASYM
Asym.
Delay
L1
L2
L3
For all the functions the LEDs MIN and MAX are flashing alternating, 
when the minimum value for the measured voltage was chosen to be 
greater than the maximum value.
If a failure already exists when the device is activated, the output relay 
remains in off-position and the LED for the corresponding threshold is 
illuminated.
Under voltage monitoring (UNDER, UNDER+SEQ)
When the measured voltage (mean value of phase-to-phase voltages) 
falls below the value adjusted at the MIN-regulator, the set interval 
of the tripping delay (DELAY) begins (red LED MIN flashes). After 
the interval has expired (red LED MIN illuminated), the output relay 
switches into off-position (yellow LED not illuminated). The output re-
lay again switches into on-position (yellow LED illuminated), when the 
measured voltage exceeds the value adjusted at the MAX-regulator.
Loss of neutral wire by means of evaluation of asymmetry
A break of the neutral wire between power line and machinery is de-
tected as soon as asymmetry between phase-to-phase voltage and 
neutral wire occurs. If the asymmetry exceeds the value set at the 
ASYM-regulator, the set interval of the tripping delay (DELAY) begins 
(red LED ASYM flashes). After the interval has expired (red LED 
ASYM illuminated), the output relay switches into off-position (yellow 
LED not illuminated). A break of the neutral wire between our device 
and the machinery can not be detected.
Phase sequence monitoring (SEQ)
Phase sequence monitoring is selectable for all functions.
If a change in phase sequence is detected (red LED SEQ illumi-
nated), the output relay switches into off-position immediately (yellow 
LED not illuminated).
L1
L2
L3
LED SEQ
Window function (WIN, WIN+SEQ)
The output relay switches into on-position (yellow LED illuminated) 
when the measured voltage (mean value of phase-to-phase voltages) 
exceeds the value adjusted at the MIN-regulator. When the measured 
voltage exceeds the value adjusted at the MAX-regulator, the set 
interval of the tripping delay (DELAY) begins (red LED MAX flashes). 
After the interval has expired (red LED MAX illuminated), the output 
relay switches into off-position (yellow LED not illuminated). The 
output relay again switches into on-position (yellow LED illuminated) 
when the measured voltage falls below the value adjusted at the 
MAX-regulator (red LED MAX not illuminated). When the measured 
voltage falls below the value adjusted at the MIN-regulator, the set 
interval of the tripping delay (DELAY) begins again (red LED MIN 
flashes). After the interval has expired (red LED MIN illuminated), the 
output relay switches into off-position (yellow LED not illuminated).
LED SEQ
Delay
L1
L2
L3
Phase failure monitoring (SEQ)
If one of the phase voltages fails, the set interval of the tripping delay 
(DELAY) begins (red LED SEQ flashes). After the interval has expired 
(red LED SEQ illuminated), the output relay switches into off-position 
(yellow LED not illuminated).
Reverse voltages of a consumer (e.g. a motor which continues to run 
on two phases only) do not effect the disconnection but can be moni-
tored by using a proper value for the asymmetry.