Tele 1341500 E3LM10 Gamma Fill Level Monitoring Relay Fill level monitoring 1341500 Scheda Tecnica

Codici prodotto
1341500
Pagina di 3
Subject to alterations and errors
Release 11/06
Monitoring relays - ENYA series
Level monitoring of conductive liquids
Multifunction
Secure isolation of the measuring circuit
1 change over contacts
Width 35mm
Installation design
Technical data
1. Functions
Level monitoring of conductive liquid, timing for tripping delay and turn-off 
delay seperatly adjustable and the following functions (selectable by 
means of rotary switch):
Pump up   
pump up or minimum monitoring
Pump down 
pump down or maximum monitoring
2. Time ranges
  
 
Adjustment 
range
Tripping delay (Delay ON): 
     0.5s to 10s
Turn-off delay (Delay OFF): 
     0.5s to 10s
3. Indicators
Green LED ON: 
indication of supply voltage
Yellow LED ON/OFF: 
indication of output relay
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-rail TS 35 according to EN 50022
Mounting position: 
any
Shockproof terminal connection according to VBG 4 (PZ1 required), 
IP rating IP20
Tightening torque: 
max. 1Nm
Terminal capacity:
 
1 x 0.5 to 2.5mm² with/without multicore cable end
 
1 x 4mm² without multicore cable end
 
2 x 0.5 to 1.5mm² with/without multicore cable end
 
2 x 2.5mm² flexible without multicore cable end
5. Input circuit
Terminals: A1-A2
Rated voltage Un: 
see table ordering information or
 
printing on the unit
Tolerance: 
-15% of +10% of Un
Rated consumption: 
2VA (1.0W)
Rated frequency: 
AC 48 to 63Hz
Duty cycle: 
100%
Reset time: 
500ms
Hold-up time: 
-
Drop-out voltage: 
>30% of supply voltage
Overvoltage category: 
III (in accordance with IEC 60664-1)
Rated surge voltage: 
6kV
6. Output circuit
1 potential free change over contact
Rated voltage: 
250V AC
Switching capacity: 
1250VA AC1 B300/P300
 
(in accordance with IEC 60947-5-1)
 
therm. constant current 5A
Fusing: 
5A fast acting
Mechanical life: 
20 x 10
6
 operations
Electrical life: 
2 x 10
5
 operations
 
at 1000VA resistive load
Switching frequency: 
max. 6/min at 1000VA resistive load
 
(in accordance with IEC 60947-5-1)
Overvoltage category: 
III. (in accordance with IEC 60664-1)
Rated surge voltage: 
6kV
7. Measuring circuit
Measuring input: 
conductive probes
 
(Type SK1, SK2, SK3)
Terminals: E1-E2-E3
Sensitivity: 0,25 
to 
100k
Ω (4mS to 10µS)
Sensor voltage: 
12V AC
Sensor current: 
max. 7mA
Wiring distance (capacity of cable 100nF/km):
 
max. 1000m (set value <50%)
 
max. 100m (set value 100%)
Overvoltage category: 
III (in accordance with IEC 60664-1)
Rated surge voltage: 
6kV
8. Accuracy
Base accuracy: 
-
Adjusting accuracy: 
-
Repetition accuracy: 
-
Voltage influence: 
-
Temperature influence: 
-
9. Ambient conditions
Ambient temperature: 
-25 to +55°C
Storage temperature: 
-25 to +70°C
Transport temperature: 
-25 to +70°C
Relative humidity: 
15% to 85%
 
(in accordance with IEC 60721-3-3  
 class 
3K3)
Pollution degree: 
2, if built in 3
 
(in accordance with IEC 60664-1)
10. Weight
Single packing: 
 
140g
E3LM10