Tele 1340403 E1YU400V01 Gamma 3-Phase Voltage Monitoring Relay 3-phase voltage monitoring 1340403 Scheda Tecnica

Codici prodotto
1340403
Pagina di 2
Subject to alternations and errors
Release 05/06
Monitoring relays - ENYA series
Voltage monitoring in 3-phase mains
Undervoltage monitoring
Supply voltage = measured voltage
1 change over contact
Width 17.5 mm
Installation design
Technical data
1. Functions
Undervoltage monitoring in 3-phase mains (each phase against the 
neutral wire) with fi xed adjustable hysteresis.
2. Time range
  
Adjustment 
range
Tripping delay: 
fixed, approx. 200ms
3. Indicators
Type E1YF:
     Yellow LED ON/OFF:   
indication of relay output
Type E1YU, E1YF400VT01:
     Green LED L1 ON/OFF: 
indication of supply voltage L1-N
     Green LED L2 ON/OFF: 
indication of supply voltage L2-N
     Green LED L3 ON/OFF: 
indication of supply voltage L3-N
     Yellow LED ON/OFF:   
indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-rail TS 35 according to EN 50022
Mounting position: 
any
Shockproof terminal connection according to VBG 4 (PZ1 required), 
IP rating IP20
Tightening torque: 
max. 1Nm
Terminal capacity:
 
1 x 0.5 to 2.5mm² with/without multicore cable end
 
1 x 4mm² without multicore cable end
 
2 x 0.5 to 1.5mm² with/without multicore cable end
 
2 x 2.5mm² flexible without multicore cable end
5. Input circuit
Supply voltage: 
(=measured voltage)
Terminals: N-L1-L2-L3
Rated voltage Un: 
see table ordering information or 
 
printing on the unit
Tolerance: 
-30% to +10% of Un
Rated consumption: 
     E1YF: 
5VA (0,6W)
     E1YU: 
8VA (0,8W)
Rated frequency: 
AC 48 to 63Hz
Duty cycle: 
100%
Reset time: 
500ms
Hold-up time: 
-
Drop out voltage: 
determined by undervoltage detection 
 
(see measured circuit)
Overvoltage category: 
III (according to IEC 60664-1)
Rated surge voltage: 
4kV
6. Output circuit
1 potential free change over contact
Rated voltage: 
250V AC
Switching capacity: 
1250VA (5A / 250V)
Fusing: 
5A fast acting
Mechanical life: 
20 x 10
6
 operations
Electrical life: 
2 x 10
5
 operations
 
at 1000VA resistive load
Switching frequency: 
max. 60/min at 100VA resistive load
 
max. 6/min at 1000VA resistive load
 
(according to IEC 947-5-1)
Overvoltage category: 
III. (according to IEC 60664-1)
Rated surge voltage: 
4kV
7. Measuring circuit
Measuring variable: 
AC sinus, 48 to 63Hz
Measuring input: 
(=supply voltage)
Terminals: N-L1-L2-L3
Overload capacity: 
determined by tolerance 
 specifi ed for supply voltage
Input resistance: 
-
Switching threshold Us: 
see table ordering information or
 
printing on the unit
Hysteresis H: 
approx. 5%
Overvoltage category: 
III (according to IEC 60664-1)
Rated surge voltage: 
4kV
8. Accuracy
Base accuracy: 
±5% (E1YU) of rated voltage
Adjustment accuracy: 
-
Repetition accuracy: 
≤2%
Voltage influence: 
-
Temperature influence: 
≤1%
9. Ambient conditions
Ambient conditions: 
-25 to +55°C (according to IEC 68-1)
Storage temperatur: 
-25 to +70°C
Transport temperature: 
-25 to +70°C
Relative humidity: 
15% to 85%
 
(according to IEC 721-3-3 class 3K3)
Pollution degree: 
2, if built-in 3
 
(according to IEC 664-1)
Vibration resistance: 
10 to 55 Hz 0.35mm
 
(according to IEC 68-2-6)
Shock resistance: 
15g 11ms
 
(according to IEC 68-2-27)
10. Weight
Single packing: 
 
72g
Packing of 10pcs: 
 
670g per Package
E1YF, E1YU