Tele 1340403 E1YU400V01 Gamma 3-Phase Voltage Monitoring Relay 3-phase voltage monitoring 1340403 Scheda Tecnica

Codici prodotto
1340403
Pagina di 2
Änderungen und Irrtümer vorbehalten
Subject to alternations and errors
www.tele-power-net.com
Types
Rated voltage Un
Threshold voltage Us Options
LEDs
Part Nr. (PQ 1) Part Nr. (PQ 10)
E1YF400V01 0.85
3N~400/230V
accord. to VDE 0108
fixed 195,5V (L- N)
Rel.
1340402
1340402A
E1YU400V01
3(N)~400/230V
160 - 240V (L-N)
L1, L2, L3, Rel. 1340403
E1YF400VT01 0.85
3N~400/230V
accord. to VDE 0108
fixed 195,5V (L- N)
L1, L2, L3, Rel.
Test function
-
-
1340406
Undervoltage monitoring for 3-phase AC mains with fixed (E1YF) or 
variable (E1YU) threshold voltage and fixed hysteresis.
All measuring inputs (L1, L2 and L3) must be connected to phase 
voltage.
If single or 2-phase monitoring is required, unused input terminals (L) 
must be connected to mains voltage to have proper L-N voltage on the 
terminals L1, L2 and L3.
A phase failure can not be detected, if the reverse voltage coming from 
the load exceeds the threshold Us.
Us
H
R
L1 L2
11
12 14
R
N L3
12 14
11
L1
L2
L3
N
L1 L2
11
12 14
R
N L3
12 14
11
L
N
1~
3N~
Undervoltage monitoring
The output relay R switches into on-position (yellow LED illuminated), 
when the measuring voltage of all connected phases exeeds the fixed 
threshold by more than the fixed hysteresis. When the voltage of one of 
the connected phases falls below the fixed threshold, the output relay R 
switches into off-position again (yellow LED not illuminated).
Test function (optional)
The test function enables a manually disconnection of the output relay.
Functions
Connections
Ordering information
E1YF, E1YU
Dimensions
17,5mm
60mm
87m
m
44mm
5mm
45mm