HP Performance Optimized Data Center (POD) 20cp Manuale Di Servizio

Pagina di 81
 
Removal and replacement procedures  52 
Humidifier 
The humidifier is located in the cold aisle humidifier bump out. 
 
You need a Phillips-head screwdriver for installation. 
 
Removing the humidifier 
1. 
Hold the drain button on the humidifier exterior until the humidifier cylinder drains completely. 
2. 
Press the power button on the outside of the humidifier to power down the humidifier. 
3. 
Close the water supply isolation valve on the HP POD 20c exterior. 
4. 
Disconnect the water supply line to the humidifier on the HP POD 20c exterior to relieve the water 
pressure. 
5. 
Open and danger tag the associated circuit breaker in the ECS cabinet. The circuit breakers are 
identified on the panel schedule.