HP Performance Optimized Data Center (POD) 20cp Manuale Di Servizio

Pagina di 81
 
Regulatory information  74 
 
The electrical connections of the HP POD 20c are evaluated as feeder connections for connection to an 
existing facility, and are not suitable as "service entrance" for connection to the utility. 
 
The HP POD 20c is designed for stationary installation outdoors in a Pollution Degree 3 environment, 
in restricted access locations, with field wiring terminals provided for permanent supply connections. 
 
The HP POD 20c meets the following ratings. 
 
Feature 
Specification 
Category 
Rated Overvoltage Category III 
Protection 
Surge protection device 
Class 
Class1 
Ambient temperature 
2°C to 54°C (35.6°F to 129.2°F) 
Relative humidity 
0% to 100% humidity 
 
 
As part of the overall certification, relevant sections of the International Building Code have been 
applied as part of the design and evaluation. The current design supports wind loads up to 90 mph. 
 
Regulatory requirements for EXIT signs 
Manufacturers of tritium EXIT signs are “specific licensees,” meaning they are licensed by the NRC or an 
Agreement State. The signs are considered “generally licensed devices,” because they are inherently safe 
enough to be handled or used by anyone with no radiation training or experience. Although purchasers – 
known as “general licensees” – do not need authorization from the NRC or a state regulatory agency to 
possess the signs, they are subject to certain regulatory requirements regarding handling, transfer or disposal 
of the signs. For more information, see the NRC website 
). They are also subject 
to NRC or Agreement State inspection and enforcement action (including fines) for violating those 
requirements. Manufacturers must inform purchasers of the EXIT signs of the regulatory requirements for 
generally licensed devices. The general licensee is required to designate an individual responsible for 
complying with the regulatory requirements. 
Under NRC regulations, a general licensee using tritium EXIT signs: 
 
must NOT remove the labeling or radioactive symbol, or abandon a sign;   
 
must properly dispose of an unused sign (see below);  
 
must report to the NRC or the appropriate Agreement State any lost, stolen or broken signs;  
 
must inform the NRC or an Agreement State of a name change, change of address or replacement of 
a general licensee’s designated representative;   
 
must NOT give away or sell the sign to another individual, company or institution unless the device is 
to remain in use at its original intended location; in such a case, the transferor is to notify the recipient 
of the regulatory requirements and must notify the NRC or Agreement State of the transfer within 30 
days.  
Tritium EXIT signs must NOT be disposed of as normal trash. To dispose of a sign properly, a general licensee 
must transfer the sign to a specific licensee. This would typically be a manufacturer, distributor, licensed 
radioactive waste broker, or a licensed low-level radioactive waste disposal facility. These facilities may 
charge a fee for this service. 
Within 30 days of disposing of a sign, the general licensee is required to file a report to the NRC or 
Agreement State that includes: