SPILLLVL
 – Sets the Spill Alarm level, adjustable from no lower than 
the Leak Alarm level to a maximum value of 500 ppm, but not higher 
than the Evacuate Alarm level. Factory default is 300 ppm. Refer to 
Appendix for recommended alarm settings for other gases. Use the 
Keypad  to set the desired Spill Alarm level, and then press ENTER  to 
save that level and return to the previous screen. 
 
EVACLVL
 – Sets the Evacuate Alarm level, adjustable from no lower 
than the Spill Alarm level to 9999 ppm. Factory default is 500 ppm. 
Refer to Appendix for recommended alarm settings for other gases. Use 
the  Keypad  to set the desired spill level alarm level, and then press 
ENTER to save that level and return to the previous screen. 
 
LOG INT
  –  Sets the interval at which measurements are logged to 
memory from 1 to 9999 minutes. Factory default is 10 minutes. Note that 
the logged measurements can be viewed using the PPM LOG function. 
Use the Keypad  to enter the desired value, and then press ENTER  to 
save that value and return to the previous screen. 
 
LOOP
  –  Adjusts the loop factor of the 4–20 mA current loop. Factory 
default is 0.016 mA per ppm, which provides an output range of 0 ppm 
(4 mA) to 1,000 ppm (20 mA). Use the Keypad  to set the desired loop 
factor, and then press ENTER  to save that value and return to the 
previous screen. 
To facilitate loop zero and span checking, note that when the LOOP 
function is selected the loop output is set to 20 mA, and upon exiting this 
function the loop output is set to 4 mA. 
 
AUDALRM
  –  Allows the monitor’s internal audible alarm to be 
associated with any function of the monitoring system. Factory default is 
OFF. Use the Keypad to select the desired audible alarm function, and 
then press ENTER to save that value and return to the previous screen.
  
Audible Alarm Settings: OFF, ANY ALARM, SYSTEM FAULT, LEAK ALARM, 
SPILL ALARM, EVAC ALARM, MONITOR STOPPED 
 
 
NOTE:  MONITOR STOPPED indicates there is a critical 
system fault, and the monitor is no longer functioning 
correctly. 
   
 
 
CLOCK
 – Sets the monitor’s date and time. Use the Keypad to enter 
the correct date and time, and then press ENTER to save those values 
and return to the previous screen. Note that time is displayed in a 
24 hour format, while the date is displayed as mm/dd/yy. 
 
SILENCE
  –  Used to enter a length of time for which the internal 
audible alarm and the external alarm are turned OFF when the front 
panel  SILENCE  button is pressed. The factory default is 300 seconds 
(5 minutes). If the cause of the alarm/fault has not been cleared at the 
end of this time period, the internal audible alarm and the external alarm 
device are reactivated. Use the Keypad to enter the desired time period, 
and then press ENTER  to save that value and return to the previous 
screen. 
 
SILENCE TIMEOUT 
     0300 sec 
SET DATE & TIME 
11/10/10   15:30 
AUDIBLE ALARM IS 
  OFF 
EDIT LOOP FACTOR 
  0.016 ma/PPM 
LOG INTERVAL IS 
     0010 min 
EDIT EVAC LEVEL 
     0500 PPM 
EDIT SPILL LEVEL 
     0300 PPM