3.5.  System Faults 
3.5.1.  Overview 
If a system malfunction occurs, the SZ  monitor  will detect the problem and turn ON  the  front panel 
SYSTEM FAULT  light. Additionally, an external alarm device may activate and the monitor’s internal 
audible alarm may sound if those features have been enabled (pages 14 and 22). 
3.5.2.  Clearing / Silencing a Fault Alarm 
The SYSTEM FAULT light and all other fault indicators will automatically turn OFF after the cause of the 
fault has been eliminated. 
Pressing the SILENCE button while a fault condition still exists causes the internal audible alarm and the 
external alarm device that is connected to the fault relay to turn OFF for a period of time as set by the 
SILENCE function (page 22). The front panel SYSTEM FAULT light remains ON, however, as a reminder 
that a fault condition still exists. The alarm circuit will reactivate at the end of the silence period if the 
cause of the fault has not been corrected. The SYSTEM FAULT light will automatically turn OFF once the 
fault has been cleared. 
3.5.3.  Viewing the Fault Log 
From the Data Display screen, use the Keypad buttons to place the arrow (>) on the display next to the 
FAULTS function. Then press ENTER to display the fault log. 
The fault log shows the monitor’s current fault status. If the fault is still 
present when the FAULTS function is selected, then the current cause of 
the fault is displayed along with the date and time it occurred. If the cause 
of the fault has been cleared, then the fault log will show <0000> along 
with the date and time the fault was cleared. Use the keypad  buttons to 
scroll through the fault log. In the examples shown to the left, record #03 
shows that a Zone Flow Fault (fault code <0800>) occurred on 11/12/10 
at 08:17, while record #04 shows that the fault was cleared on 11/12/10 at 
8:30. 
The cause of the fault is identified by a numeric fault code.  To convert the 
fault code into a text description of the fault, first press the ENTER button 
and then use the Keypad  buttons to scroll through the display until the 
text description of the fault appears. If the fault code is a combination of 
two or more faults, then continue to use the Keypad buttons until all fault 
text descriptions have been displayed.   For example, the fault code 
<1800> represents the combination of both a Zone Flow <0800> and a 
Purge Flow <1000> fault as shown to the left. 
Note that the Fault Log can be cleared as described on page 25. 
#03 <0800> @ 
11/12/10  08:17 
FAULT CODE<1800> 
12     ZONE FLOW 
FAULT CODE<1800> 
13    PURGE FLOW 
#04 <0000> @ 
11/12/10  08:30