HP Performance Optimized Data Center (POD) 20cp Guida All'Installazione
Supported facility connections 19
Supported facility connections
Humidifier specifications
A dedicated supply of domestic water is required if the optional humidifier is installed. For exact
requirements for the humidifier model that was installed, see the humidifier manual supplied with the HP
POD.
requirements for the humidifier model that was installed, see the humidifier manual supplied with the HP
POD.
Item
Component
1
Humidifier drain
2
Water supply
For more information about the humidifier, see the documentation developed by the humidifier
manufacturer.
manufacturer.
Convenience outlets
The HP POD is prewired for a convenience outlet on the inside of the unit. This circuit is not part of the
power provided by the main switchboard feeding the 3-phase power to the HP POD. To energize this
circuit, you must supply a dedicated single phase, 16-or 20-amp branch circuit from your facility at the
appropriate voltage. Make sure that the branch circuit is connected to the prewired exterior mounted
junction box and must be wired in accordance with local regulations and codes.
power provided by the main switchboard feeding the 3-phase power to the HP POD. To energize this
circuit, you must supply a dedicated single phase, 16-or 20-amp branch circuit from your facility at the
appropriate voltage. Make sure that the branch circuit is connected to the prewired exterior mounted
junction box and must be wired in accordance with local regulations and codes.
Grounding requirements
The neutrals and equipment grounding conductors for all 3-phase HP POD feeders must remain isolated.
The two conductors can be bonded at the power source only.
The two conductors can be bonded at the power source only.