HP Performance Optimized Data Center (POD) 20cp Guida All'Installazione

Pagina di 22
 
Supported facility connections  19 
Supported facility connections 
Humidifier specifications 
A dedicated supply of domestic water is required if the optional humidifier is installed. For exact 
requirements for the humidifier model that was installed, see the humidifier manual supplied with the HP 
POD. 
 
 
Item 
Component 
Humidifier drain 
Water supply 
 
For more information about the humidifier, see the documentation developed by the humidifier 
manufacturer. 
 
Convenience outlets 
The HP POD is prewired for a convenience outlet on the inside of the unit. This circuit is not part of the 
power provided by the main switchboard feeding the 3-phase power to the HP POD. To energize this 
circuit, you must supply a dedicated single phase, 16-or 20-amp branch circuit from your facility at the 
appropriate voltage. Make sure that the branch circuit is connected to the prewired exterior mounted 
junction box and must be wired in accordance with local regulations and codes. 
 
Grounding requirements 
The neutrals and equipment grounding conductors for all 3-phase HP POD feeders must remain isolated. 
The two conductors can be bonded at the power source only.