HP Performance Optimized Data Center (POD) 20cp Guida All'Installazione

Pagina di 22
 
Site requirements  8 
Features 
Specifications 
Nonoperating 
temperature* 
-29ºC to 54ºC (-20ºF to 130ºF) 
Operating humidity 
 
0% to 100% relative noncondensing 
Nonoperating humidity* 
 
5 to 95% relative noncondensing 
 
39ºC (102ºF) maximum wet bulb temperature 
Operating altitude 
-76.2 to 3,048 m (-250 to 10,000 ft) 
Non-operating altitude 
-76.2 to 9,144 m (-250 to 30,000 ft) 
 
*For nonoperating specifications, consider the temperature of computer and IT equipment inside the HP POD. 
The HP POD must be drained before it is moved to a new location. 
For areas prone to freezing, take appropriate water freeze protection precautions. 
 
Lightning protection 
If the HP POD is installed in an outdoor environment, then HP recommends hiring a lightning protection 
consultant to evaluate potential lightning risks and assess possible HP HP POD lightning protection 
schemes.