HP Performance Optimized Data Center (POD) 20cp Guida All'Installazione Rapida
Supported facility connections 18
HP POD 20c access control
The HP POD 20c is equipped with standard key lock hardware for each personnel entry door and external
electrical cabinet. Each personnel entry door includes a door access contact that can be connected to the
electrical cabinet. Each personnel entry door includes a door access contact that can be connected to the
customer facility security system.
Additional options for controlled access include the following:
Additional options for controlled access include the following:
•
Electronic card reader
•
12-digit access control code keypad
•
Magnetic lock on each personnel access door and dynamic hot aisle door
Fire, safety, and access notifications
Dry contacts are provided to enable the connection between the HP POD 20c and the customer’s facility. If
the HP POD 20c is connected to the customer facility systems, then the alarm conditions of the HP POD 20c
the HP POD 20c is connected to the customer facility systems, then the alarm conditions of the HP POD 20c
can be detected by the facility systems.
It is your responsibility to facilitate these connections. HP can make these connections when specifically
It is your responsibility to facilitate these connections. HP can make these connections when specifically
contracted to deliver these services and a Scope of Work has been drafted, reviewed, and signed for
delivery services.
The customer must provide an independent connection for each system listed in the following table.
delivery services.
The customer must provide an independent connection for each system listed in the following table.
Alarm
Description
Fire prevention alarm Smoke is detected in the HP POD 20c.
Fire suppression
Fire suppression
system (optional)
The suppression system alarm is activated and gas is
dispersed to suppress a fire.
Access control
A door of the POD has been opened.
EPO
The EPO system is activated by manually pressing the
EPO button or by a thermal event, and the HP POD 20c
is shut down.
EPO button or by a thermal event, and the HP POD 20c
is shut down.
The electrical layout of the fire alarm system is described in the schematic drawing that is supplied with the
HP Performance Optimized Datacenter 20c Site Drawing Package.
Fire box
The communication connections between the fire system and the HP POD 20c are made through the fire box.