HP Performance Optimized Data Center (POD) 20cp Guida All'Installazione Rapida

Pagina di 38
 
Supported facility connections  18 
HP POD 20c access control 
The HP POD 20c is equipped with standard key lock hardware for each personnel entry door and external 
electrical cabinet. Each personnel entry door includes a door access contact that can be connected to the 
customer facility security system. 
Additional options for controlled access include the following: 
• 
Electronic card reader 
• 
12-digit access control code keypad 
• 
Magnetic lock on each personnel access door and dynamic hot aisle door 
 
Fire, safety, and access notifications 
Dry contacts are provided to enable the connection between the HP POD 20c and the customer’s facility. If 
the HP POD 20c is connected to the customer facility systems, then the alarm conditions of the HP POD 20c 
can be detected by the facility systems. 
It is your responsibility to facilitate these connections. HP can make these connections when specifically 
contracted to deliver these services and a Scope of Work has been drafted, reviewed, and signed for 
delivery services. 
The customer must provide an independent connection for each system listed in the following table. 
  
Alarm 
Description 
Fire prevention alarm  Smoke is detected in the HP POD 20c. 
Fire suppression 
system (optional) 
The suppression system alarm is activated and gas is 
dispersed to suppress a fire. 
Access control 
A door of the POD has been opened. 
EPO 
The EPO system is activated by manually pressing the 
EPO button or by a thermal event, and the HP POD 20c 
is shut down. 
 
The electrical layout of the fire alarm system is described in the schematic drawing that is supplied with the 
HP Performance Optimized Datacenter 20c Site Drawing Package
 
Fire box 
The communication connections between the fire system and the HP POD 20c are made through the fire box.