Benefits
The new EX2100 Alterrex diode bridge product can be installed
with a new EX2100 Alterrex digital voltage regulator. Replacing
the aging analog controls provide improved diagnostics and
monitoring of the new diode bridges as well as a host of other
performance, diagnostic and reliability features. Your GE sales
representative can provide additional information on the entire
portfolio of EX2100 generator control and GP2100r generator
protection products and services.
Concern
Original ALTERREX Rectifier
New EX2100 Rectifier
Erosion of copper pipes
Significant problem. Voltages rapidly drive
ions into the de-ionized cooling water, causing
erosion.
Eliminated. All wetted surfaces are stainless
(erodes < 10% as quickly as copper) or
elastomer. Heat-sink is grounded, eliminating
“ion-driving.”
Leaks or blockages at connection
points
Significant problem. Depending on the specific
model, there are between 20 to 30 hoses per
cubicle. Some are small and easily blocked.
Greatly reduced. Only four hoses/bridge
positioned where minor leaks will not cause
a fault/trip. Large hose diameters make
blockages unlikely.
Copper tracking along Teflon tubes
Significant problem. Voltages cause copper to
track along the inside of the short Teflon tubes.
Eliminated entirely. No Teflon tubes or
voltages present to drive tracking
Bridge diagnostics
Unreliable. Neon lights used for failed-cell
indication fail more often than the cells.
Increased reliability. New blown-fuse indicator
and single-light with test button is reliable
and less susceptible to false positives.
Bridge repair time
Long. The product is crowded and has many
water hoses. Also, maintaining diode clamp
alignment is tricky.
Short. Easy access to diodes and fuses, and
no clamps. Easy access to water hoses.
Product cost
Fairly high. Many expensive and custom parts.
Low. Mostly industry standard parts except
for the heat sink
Installation time
Medium. Time-consuming process to remove
and replace old, eroded parts
Low. Fewer parts and fewer hoses. New wiring
harnesses.
Features
• Minimum water carrying parts
– One aluminum heat-sink (with a single continuous
stainless-steel tube)
– Two ball valves
– Four industry standard hydraulic hoses
• High-reliability materials: no more copper, brass,
or bronze anywhere
– Only stainless steel or durable, stainless braid protected
elastomer hose
• High-quality valves and fittings: quick disconnect connections
and no rust-prone gate valves
• Standard hydraulic fittings: off-the-shelf products,
not high-cost long cycle components
• Easy to repair with all front accessible components