A.  Brick Masonry
 
Minimum  3.5-inch  thick  brick  masonry  all  framed 
into combustible wall with a minimum of 2-inch brick 
separation from clay liner to combustibles. The fireclay 
liner shall run from outer surface of brick wall to, but 
not beyond, the inner surface of chimney flue liner and 
shall be firmly cemented in place.
B.  Insulated Sleeve
 
Solid-insulated, listed factory-built chimney length of 
the same inside diameter as the chimney connector and 
having 1-inch or more of insulation with a minimum  
9-inch air space between the outer wall of the chimney 
length and combustibles.
C.  Ventilated Thimble
 
Sheet steel chimney connector, minimum 24 gauge in 
thickness, with a ventilated thimble, minimum 24 gauge 
in thickness, having two 1-inch air channels, separated 
from  combustibles  by  a  minimum  of  6-inch  of  glass  
fiber insulation. Opening shall be covered, and thimble 
supported with a sheet steel support, minimum 24 gauge 
in thickness.
D.  Chimney Section Pass-through
 
Solid insulated, listed factory-built chimney length with 
an inside diameter 2-inch larger than the chimney con-
nector and having 1-inch or more of insulation, serving 
as a pass-through for a single wall sheet steel chimney 
connector  of  minimum  24  gauge  thickness,  with  a 
minimum  2-inch  air  space  between  the  outer  wall  of 
chimney section and combustibles. Minimum length of 
chimney section shall be 12-inch chimney section spaced  
1-inch away from connector using sheet steel support 
plates on both ends of chimney section. Opening shall 
be  covered,  and  chimney  section  supported  on  both 
sides with sheet steel support securely fastened to wall  
surfaces  of  minimum  24  gauge  thickness.  Fasteners 
used  to  secure  chimney  section  shall  not  penetrate  
chimney flue liner.
ChImNEY CONNECTOR SYSTEmS & ClEARANCES