Trane OA1D OA2D OA3D (Indirect Gas-Fired/Electric Heat) Manuale Di Manutenzione

Pagina di 56
System Configuration and Pre-Start
34
 OAU-SVX01E-EN
Table 9.
Menu descriptions 
Screen
Menu
Point List
Min/Inactive
Default
Max/Active
BAS 
Point?
Alarms
Active Alarms
List of all active alarms
All Alarms
List of all previous alarms
Reports 
(continued 
on next 
page)
Custom Graphics
*NOT USED*
System Status
Program Control
Discharge Air Control Space Control
Space  Control
Y
Heat Cool Mode Active
Heat
---
Cool
N
Occupancy Status
Occupied|Unoccupied|Occupied Bypass|Occupied Standby|Unknown Y
Compressor 1 Command
Off
---
On
N
Compressor 2 Command
Off
---
On
N
Compressor 3 Command
Off
---
On
N
Compressor 4 Command
Off
---
On
N
Digital Scroll Command
0%
---
100%
N
Dehumidification Command
Disabled
Enabled
N
Discharge Air Temperature Local
Analog Input
Economizer Mode
Disabled
Enabled
N
Evap Leaving Temp Local
Analog Input
Heat Capacity
0%
---
100%
N
Heating Output Command
0%
---
100%
N
Heat 1 Command
Off
---
On
N
Heat 2 Command
Off
---
On
N
Heat 3 Command
Off
---
On
N
Inducer Command
Off
---
On
N
Gas Valve Status
Binary Input
HGRH Command
0%
---
100%
N
OA Damper End Switch
Binary Input
Outdoor Air Damper Command
Closed
---
Open
N
OAD Position Local
Binary Input
Outdoor Air Relative Humidity Local
Analog Input
Outdoor Air Temperature Local
Analog Input
Space Dewpoint Active
Analog Input
Space Temperature Local
Analog Input
Supply Fan Start Stop Command
Off
---
Off
N
Filter Status
Clean
---
Dirty
N
System Lockout
Normal
Normal
Lockout
N
UNOCC Cooling Mode
Off
---
On
N
UNOCC Dehumid Mode
Off
---
On
N
UNOCC Heating Mode
Off
---
On
N
ERV Command
Disable
---
Enable
N
ERV Leaving Air Temperature Local
Analog Input
PEVFD Command
0%
80%
100%
Y
Discharge Airflow Local
Analog Input
ERV Leaving Air Humidity Local
Analog Input