Trane OA1D OA2D OA3D (Indirect Gas-Fired/Electric Heat) Manuale Di Manutenzione

Pagina di 56
System Configuration and Pre-Start
OAU-SVX01E-EN
35 
Reports 
(continued 
from 
previous 
page)
System Setpoints
DAT High Temp Cutout
100°F
125°F
150°F
Y
DAT Low Temp Cutout
35°F
35°F
50°F
Y
DAT Temp Cutout Time
10 min.
10 min.
25 min.
Y
Discharge Air Cooling Setpoint
55°F
55°F
75°F
Y
Discharge Air Heating Setpoint
65°F
85°F
90°F
Y
ERV Wheel Frost Cutout Setpoint
32°F
34°F
40°F
Y
EVAP Leaving Temp Setpoint
45°F
53°F
70°F
Y
IVFD Signal
50%
100%
100%
Y
Maximum Discharge Air Temperature
70°F
90°F
100°F
Y
Minimum Discharge Air Cooling Setpoint 40°F
50°F
65°F
Y
Minimum Discharge Air Heating Setpoint 50°F
55°F
60°F
Y
Maximum OA Damper Position
0%
100%
100%
Y
Minimum OA Damper Position
0%
100%
100%
Y
Occupied Space Cooling Setpoint
65°F
74°F
90°F
Y
Occupied Space Heating Setpoint
60°F
70°F
75°F
Y
Outdoor Air Cooling Setpoint (OACS)
70°F
75°F
85°F
Y
Outdoor Air Dewpoint Setpoint (OADS)
49°F
58°F
65°F
Y
Outdoor Air Heating Setpoint (OAHS)
40°F
70°F
70°F
Y
PEVFD Setpoint
0%
80%
100%
Y
Space Dewpoint Setpoint (SPDS)
50°F
59°F
68°F
Y
UNOCC Space Cooling Setpoint
60°F
80°F
90°F
Y
UNOCC Space Dewpoint Setpoint
49°F
65°F
68°F
Y
UNOCC Space Heating Setpoint
50°F
60°F
70°F
Y
System Setup
Program Control
Discharge Air Control Space Control
Space  Control
Y
Compressor  Count
0
0
4
N
Heater  Count
0
0
2
N
Split Manifold Burner
Not Installed
Installed
Installed
N
ERV Option
Not Installed
Installed
Installed
N
Powered Exhaust Option
Not Installed
Installed
Installed
N
Return Air Damper Option
Not Installed
Installed
Installed
N
Space Temp/Humidity Sensor Installed
Not Installed
Installed
Installed
N
Heat Type
No Heat|Gas Heat|Electric Heat|Other
N
Alarm Reset
Off
Off
On
Y
Supply Fan Failure Reset
Off
Off
On
Y
Override Summary List of active overrides - same as selecting Override button at top of screen
All Point Report
List of all points (AO/AI/BO/BI/MS/etc …) in the configuration file
About
Controller Name listed is the version of the program installed in the UC600
Expansion Modules Provides status of expansion modules
TGP2 Programs
List of all TGP2 programs loaded on the UC600
Data Graphs *NOT USED*
Settings
Schedules - Refer to UC600 IOM for scheduling functions
Display Preferences
Language
Date and Time
Clean Touchscreen
Table 9.
Menu descriptions (continued)
Screen
Menu
Point List
Min/Inactive
Default
Max/Active
BAS 
Point?