(3) Run all applicable tests before assuming Module or Compressor to be faulty. 
B: Compressor Not Running, No Start Attempt. 
 
   
  
 Probable cause 
Action 
Supply voltage too low 
Check voltage with a digital multi-meter 
at the terminals on the Module. This 
must be 11.7v or more for a 12v supply 
& 24v or more for a 24v supply. Inspect 
power supply, ground connections & 
components for integrity. Check wire 
sizing. Charge batteries if necessary. 
2   Supply voltage too high 
If a 12v supply is faulty & delivers over 
17v, the compressor will not run. If it is 
over 24v, it will assume that it is a 24v 
supply & act accordingly. 
Polarity incorrect 
Check that the polarity is correct at the 
Module. 
Faulty thermostat 
Remove the thermostat wires & jumper 
the terminals that they were on together 
temporarily. If the system then runs, 
make the connection permanent & 
control the system manually from the 
breaker on your supply panel. Replace 
thermostat as soon as possible. 
5 Thermostat 
wired 
incorrectly, or faulty 
connections. 
Refer to the installation instructions & 
confirm that connections are as they 
should be. Ensure that the thermostat 
connectors are pushed firmly on to the 
Module terminals.  
6 Multi-speed 
board 
incorrectly installed (if 
fitted) 
Check to make sure that the 2 
connectors at the rear of the multi-speed 
board are attached to the C & T 
terminals of the Module. 
7 Multi-speed 
board 
faulty 
(if fitted)  
** Optional Part ** 
Remove board & jumper terminals C & 
T on the Module. Note; If the thermostat 
wires are connected directly to C & T on 
the Module, the compressor will run at 
its slowest speed. 
Compressor plug not 
Disconnect the Module by removing the