Mermaid REFRIGERATION/FREEZER Manuale Utente

Pagina di 18
connected 
retaining screw & then ensure that the 3-
pin plug is seated firmly on the pins of 
the compressor. 
Faulty compressor 
Remove the Module as above, & unplug 
from the compressor. Check that ohm 
readings are the same across all 
terminals of the compressor. 
10  Heat sink overheated 
Allow components to cool down before 
attempting re-start. 
11  Compressor too cold 
If compressor is below freezing 
temperature, allow to warm up before 
attempting re-start. 
  
  
  
 
C: Compressor Attempts to Start, or Starts Then Stops Shortly After: 
 
 1  Faulty or inadequate 
power supply 
Monitor the supply voltage at the 
terminals on the Module during start 
attempts to ensure that it does not fall 
below threshold levels. If it does, check 
power supply, ground connections & 
components for integrity. Check for 
correct wire sizing. Charge batteries if 
necessary. 
2  Faulty fan or pump relay 
or unauthorized 
component installed  
Remove connectors from F & + 
terminals on Module & attempt re-start. 
Maximum current draw on these 
terminals is limited to 0.7 amps 12v 
3  Quick Connect fittings not 
made 
Check that all refrigerant fittings are 
connected together properly. 
 
D: System Runs, Box Temperature Too High: 
 1  Thermostat setting 
Rotate thermostat knob clockwise to a 
higher number. 
2 Speed 
setting 
** Optional Part **  
Check that thermostat leads are 
connected to the speed setting 
recommended for the evaporator that is 
installed, & for its use i.e. refer or 
freezer.