C: Compressor Non-Start:
  
If the compressor does not start, the Module will stop the starting process, & attempt a re-
start every 60 seconds. 
D: Compressor Speed Too Low:
  
If the compressor speed falls below 1900 RPM the Module will stop the compressor. 
E: Fan Protection:
  
If the current draw across the fan terminals exceeds 0.7 amps 12v dc, the compressor will 
be stopped & a re-start attempted every 60 seconds. 
F: Module Overheat:
  
If the heat sink on the module exceeds a preset temperature, the compressor will be 
stopped & will be re-started when normal operating temperatures are resumed. 
G: 4 Alarm Indicator: 
A LED may be installed across the + & D terminals of the Module to indicate a failure 
condition as follows: 
LCD will “Blink” up to 5 times every 5 seconds. 
1 Blink;  Supply voltage low, below 10.4v (22.8) 
2 Blinks; Excessive load on fan terminals, above 1.0 amps 
3 Blinks; Compressor non-start – Refrigerant pressure too high 
4 Blinks; Compressor speed below 1850 RPM 
5 Blinks; Module heat-sink temp too high. Re-sets on cool-down.  IE: Module too hot. 
NOTE ONE 
After power is applied to the Module there may be a delay of up to 60 seconds before the 
compressor starts