PLANNING YOUR INSTALLATION 
 
PAGE 8 
MASONRY AND FACTORY BUILT FIREPLACES  
The model Optima
 
3 INS is approved for installation into a solid 
fuel burning fireplace, either a masonry fireplace (built to UBC 37 
or ULC S628 standards) or an approved factory-built / zero 
clearance fireplace (built to UL 127 or ULC S610 standards). 
See pages 20 and 21 for additional information on venting.  
 
Minimum Fireplace Firebox Size 
Height 
20 1/8” / 512 mm 
Width @ Front 
32”        / 814 mm  
(extends back 1 ½”) 
Width @  back 
24 5/8” / 626mm 
Depth 
17 ¾”   / 452 mm 
 
 
 
CAUTION:  The fireplace in which the Optima 3 INS is to be 
installed must be thoroughly cleaned if it has been used to burn 
wood or synthetic logs. Have the chimney and all inside sur-
faces of the fireplace brushed and vacuumed so that no soot, 
embers, or loose combustion deposits can be drawn into the 
heat circulation blower and blown into the living area. If any por-
tion of the chimney system shows signs of structural or me-
chanical weaknesses, such as: cracks, leaky joints, corroded or 
warped surfaces, the faulty portion must be repaired or replaced 
prior to installing this appliance. 
 
IMPORTANT:  When installing the Optima 3 INS into a factory 
built fireplace or heatform, the air flow within and around the fire-
place shall not be altered by the installation of the insert (i.e. DO 
NOT BLOCK louvers or cooling air inlet or outlet ports, circulating 
air chambers in a steel fireplace liner or metal heat circulator). The 
factory built firebox must accept the insert without modification 
other than removing bolted or screwed together pieces such as 
smoke shelf / deflectors, ash lips, screen or door tracks and 
damper assemblies. Any fireplace component, which is removed, 
must be retained so they can be reinstalled to restore the fireplace 
to its original operating condition. The removal of any part must 
not alter the integrity of the outer shell of the pre-engineered fire-
place cabinet in any way. A Warning Label (provided with appli-
ance) must be installed in the fireplace firebox so that it shall be 
visible upon removal of the fireplace insert (see Fireplace Warning 
Label, below). Use RTV high Temperature Silicone as an adhe-
sive to affix the warning label. 
Fireplace Warning Label 
(provided in accessory package) 
 
THIS FIREPLACE HAS BEEN ALTERED TO ACCOMMO-
DATE A FIREPLACE INSERT AND SHOULD BE IN-
SPECTED BY A QUALIFIED PERSON PRIOR TO RE-
USE AS A CONVENTIONAL FIREPLACE. 
HEARTH / FLOOR PROTECTION - Optima 3 INS 
The area directly in front of the Optima 3 INS 
must be protected by a noncombustible material 
or a fireplace hearth or hearth extension as fol-
lows:  
Combustible flooring must be protected by 
non-combustible material in Canada and 10 
millimeter (3 / 8 inches) millboard or equivalent 
non-combustible in U.S. extending beneath the 
heater and to the front as indicated or to the 
nearest permitted combustible material. See 
page 6 for requirements when using alternate 
material as hearth extension. 
 
 
The protected area must extend 6” to the front of 
the face of the Optima 3 INS. 
 
MINIMUM CLEARANCES TO COMBUSTIBLES 
   
 
inches / millimeters 
A - Insert to side wall  
6”   /  153 mm 
B - Insert to side trim  
1”   /  26 mm 
C - Hearth extension 
6”   /  153 mm 
D - Insert to mantel 
18”  /  458 mm 
E - Insert to top trim 
1”   /  26 mm 
 
Top View 
 
 
Side View 
 
 
Recommended clear-
ance zone from the
front of the appliance
to combustibles is 4
feet minimum. 
24 5/8" 
17 3/4"
32" 
Clean-out 
Tee
 
 D
E
Mantel
 
Trim 
Side Wall 
Trim