HP Performance Optimized Data Center (POD) 240a Manuale Utente

Pagina di 93
 
Power, electrical, and controls  28 
 
WARNING:
  To avoid the risk of personal injury or loss of life, all personnel must comply with 
electrical warning labels when operating and maintaining the electrical panels and systems of the 
HP POD 240e NA. 
  
For the external electrical power component locations, see "Electrical power component identification (on 
page 
)." 
 
Power distribution: electrical busway system 
Each IT section of the HP POD 240e NA is protected by an electrical circuit breaker panel located on the end 
of the HP POD 240e NA. 
End view shown 
 
The following specifications are for each IT section electrical circuit breaker panel. 
 
Feature 
Specification 
Number of busways 
Frequency 
60 Hz 
Amps (per busway) 
200A 
Voltage (per busway) 
415V, wye 
Grounding 
Copper 
Busway conductors 
3-phase + neutral + equipment ground 
 
 
Power distribution: Adiabatic system 
The Adiabatic units are powered and protected by an electrical circuit breaker panel located on the end of 
the HP POD 240e NA. Within each AHU electrical cabinet, there are two panels that provide power to the 
Adiabatic units.