HP Performance Optimized Data Center (POD) 240a 사용자 설명서
Power, electrical, and controls 28
WARNING:
To avoid the risk of personal injury or loss of life, all personnel must comply with
electrical warning labels when operating and maintaining the electrical panels and systems of the
HP POD 240e NA.
For the external electrical power component locations, see "Electrical power component identification (on
page
page
)."
Power distribution: electrical busway system
Each IT section of the HP POD 240e NA is protected by an electrical circuit breaker panel located on the end
of the HP POD 240e NA.
End view shown
End view shown
The following specifications are for each IT section electrical circuit breaker panel.
Feature
Specification
Number of busways
8
Frequency
60 Hz
Amps (per busway)
200A
Voltage (per busway)
415V, wye
Grounding
Copper
Busway conductors
3-phase + neutral + equipment ground
Power distribution: Adiabatic system
The Adiabatic units are powered and protected by an electrical circuit breaker panel located on the end of
the HP POD 240e NA. Within each AHU electrical cabinet, there are two panels that provide power to the
Adiabatic units.
Adiabatic units.