Installation 23 
11. 
(Optional) Connect the HP POD humidifier to the domestic or industrial water drain (1) and supply 
(2) lines. For more information about the humidifier, see the product documentation. 
 
12. 
Perform one of the following: 
If your HP POD is located inside, HP recommends connecting each of the drains to the local 
drain line. 
If your HP POD is located outside, you can choose to connect to the local drain line, or allow the 
water to drain off freely in your location. For more information, see Drain locations ("
 
 
Connecting the power 
  
 
IMPORTANT:
  A licensed electrician must connect the power according the local electric code, 
consistent with supplier and consulting engineer drawings.  
  
1. 
Verify that the HP POD, transformer, and switchboard are in their final locations. 
2. 
Make all connections: 
Connect the main power leads from your facility to the transformer (1 to 2). 
Each connection is labeled with colored tape, according to local standard requirements. 
Connect the transformer to the switchboard (2 to 3). 
Connect the three 3-in flexible conduits from the switchboard to the junction box on the HP POD 
(3 to 4).