HP Performance Optimized Data Center (POD) 40cp Manuale Utente

Pagina di 63
 
Power management  33 
 
To disable power to a single PDU, turn off the main switch on that PDU. 
 
To disable power to a single rack, open the main breaker on the dropbox connected to the electrical 
busway. 
 
To disable power to a single electrical busway, open the appropriate main breaker for that busway 
on the corresponding electrical busway panel outside of the HP POD. 
 
Power distribution 
The standard HP POD is powered by two electrical busways on the ends of the unit. 
 
 
Standard HP POD 
Feature Specification 
Number of busways 
Frequency 60Hz 
Amps (per busway) 
400A  
Neutral Ampacity (per breaker) 
480A 
Amps derated percentage 
20% 
Max usable amps (per busway) 
320A 
Voltage (per busway) 
415V 
Grounding Aluminum 
casing 
Phases 3