HP Performance Optimized Data Center (POD) 40cp Manuale Utente
Power management 33
•
To disable power to a single PDU, turn off the main switch on that PDU.
•
To disable power to a single rack, open the main breaker on the dropbox connected to the electrical
busway.
busway.
•
To disable power to a single electrical busway, open the appropriate main breaker for that busway
on the corresponding electrical busway panel outside of the HP POD.
on the corresponding electrical busway panel outside of the HP POD.
Power distribution
The standard HP POD is powered by two electrical busways on the ends of the unit.
Standard HP POD
Feature Specification
Number of busways
2
Frequency 60Hz
Amps (per busway)
Amps (per busway)
400A
Neutral Ampacity (per breaker)
480A
Amps derated percentage
20%
Max usable amps (per busway)
320A
Voltage (per busway)
415V
Grounding Aluminum
casing
Phases 3