HP Performance Optimized Data Center (POD) 40cp Manuale Utente

Pagina di 63
 
Power management  35 
Panels 
The following panels are on the exterior of the HP POD. 
 
   
Item Component 
Description 
Electrical busway enclosed 
circuit breaker (on page 
400A enclosed circuit breakers that powers the electrical 
busways: 
 
Two electrical busway panels are activated in the 
standard HP POD. 
 
Three electrical busway panels are activated in the high 
density HP POD. 
EPO panel (on page 
Contains controls and status indicators for the EPO system 
Fire alarm panel ("
Contains controls and status indicators for the fire alarm 
system 
ASSD panel (on page 
Air sampling smoke detection system 
EPO button 
Cuts off all power to the POD and activates the EPO alarm 
lamp. 
Security panel ("
Reserved for installing interface and power requirements for 
any optional security devices installed. 
7 EPM
panel∗ ("
Electrical power monitoring system 
("
" on page 
Maintains the humidity inside the HP POD within a set range 
to minimize static electricity. 
Auxiliary Land power* 
Provides auxiliary power for the BMS or convenience outlets. 
120V owner-provided power. 
10 
BMS panel (on page 
Building Management System 
11 
Fan control (FC) panel ("
Circuit breakers that control the fan units 
12 
120A electrical panel board providing auxiliary HP POD 
electrical requirements 
13 
Junction Box 
Main input box for incoming electrical feeder cables 
 
Optional component