HP Performance Optimized Data Center (POD) 20cp Manuale Utente

Pagina di 86
 
Environmental control system  35 
By connecting your HP POD 20c to a BMS system, you can monitor the various parameters and alarms. For 
more information, see "Navigating the ECS interface (on page 
)." The complete list of parameters and 
alarms that can be monitored will be discussed with your facilities personnel. 
  
 
IMPORTANT:
  If your site does not have a BMS, HP POD 20c ECS data can be sent to and 
viewed from a set IP address. Communication occurs through an Ethernet cable that is connected 
to the demarcation box (on page 
). 
  
 
Sensors 
The HP POD 20c has several temperature sensors that monitor the environmental factors and communicate 
data back to the ECS. 
 
Humidity sensors 
Two humidity sensors monitor humidity in the cold aisle and report data to the ECS. 
 
 
Pressure sensors 
Six Beckhoff pressure sensors located in the control cabinet measure the differential pressure between the hot 
aisle and the cold aisle, as well as the air filters. These pressure sensors monitor the pressure at nine sampling 
locations throughout the HP POD 20c and report output data to the ECS. The ECS uses the calculated aisle 
differential pressures to control fan speed and uses the zone filter differential pressure to indicate when filters 
need to be replaced.