HP Performance Optimized Data Center (POD) 20cp Manuale Utente

Pagina di 86
 
Environmental control system  58 
Alarm 
Meaning 
Solution 
Leak detection 
The drain pan sensor detects 
water in the pan. 
See the HP Performance Optimized Datacenter 
20c Maintenance and Service Guide or contact 
HP service if you are still within your service 
contract. 
Change filter 
The return air filters are full. 
Replace the return air filters. For more 
information, see the HP Performance Optimized 
Datacenter 20c Maintenance and Service 
Guide
High temperature 
The cold aisle temperature has 
surpassed the setpoint 
temperature. 
Verify that you have water flowing into your 
HP POD 20c and the fans are operating. 
Contact HP service if you are still within your 
service contract. 
 
Low temperature 
The cold aisle temperature is 
too low. 
Verify that all components are operating 
normally. 
Contact HP service if you are still within your 
service contract. 
 
EPO 
The EPO system activates and 
the HP POD 20c shut down. 
Follow the emergency procedures for your 
facility. 
After the emergency is cleared, reset the 
EPO and other HP POD 20c systems. 
 
Differential pressure 
The difference in pressure 
between the hot and cold aisles 
is above the setpoints. 
Verify that the cold/hot aisle differential 
pressures are within the setpoints. 
Contact HP service if you are still within your 
service contract. 
 
 
 
Safety and access control alarms 
Alarms pertaining to the safety of the HP POD 20c are (optionally) relayed through your building fire and 
access control dispatch. 
  
Alarm 
Meaning 
Solution 
Fire alarm* 
The HP POD 20c detected a fire. 
Activate the EPO. Follow the emergency 
procedures for your facility. 
Access control alarm 
(optional) 
An access control breach occurred.  Follow the emergency procedures for your 
facility. 
EPO 
The EPO system activated and the HP 
POD 20c shut down. 
Follow the emergency procedures for your 
facility. 
 
*The fire alarm is relayed to your building fire and access control dispatch only if you have connected your facility to the 
fire box (on page 
).