HP Performance Optimized Data Center (POD) 20cp Manuale Utente

Pagina di 86
 
Cooling system  61 
 
Feature 
Specification 
Facility input temperature to the HP POD 
20c 
12º to 24ºC (55º to 75ºF) 
Max design pressure 
1,034 kPa (150 psi) 
HP POD 20c pressure drop 
172.4 kPa (25 psi) 
HP POD 20c water flow rate 
454 lpm (120 gpm*) 
Chilled water supply and return 
connections 
Two DIN PN16 DN80 flanges 
 
*Measurement is in US gallons per minute. 
 
Cooling system components 
Each of the three heat exchanger area access hatches are rated NEMA 3R for outdoor use. The exterior of 
the hatches are coated with a durable finish to protect against corrosion. The access hatches are located on 
the roof of the POD. The heat exchangers can be accessed from the roof of the POD by removing one of the 
six access hatches. 
Top view shown 
 
 
Item 
Component 
Description 
Heat exchangers 
Uses chilled facility water to cool the air in the HP POD 20c 
Chilled water supply 
header 
Provides cooled chilled water from the site chilled water system to the heat 
exchangers 
Chilled water return 
header 
Provides heated chilled water to the return site chilled water system