 6800/7000 Series - Frames and Power Supplies Installation and Operation Manual
21
LEDs
 Chapter 4: CF-6801 Cooling Frame
LEDs
A green LED indicates that power is supplied to the unit, while a red 
LED indicates a failure sensed by a contact closure.
There are five criteria for failure in the CF-6801, indicated by the LEDs 
and listed in the table below. 
See
LED Condition
Function
Over-Current Sensing (red)
If one or more of the fans short out, this LED 
illuminates and the GPI closes.
Under-Current Sensing 
(red)
If one or more of the fans open-circuit, this 
LED illuminates.
Over-Temperature Sensing 
(red)
If the temperature in the fan tray unit exceeds 
125
°
F (520
°
C), the red error LED turns on 
and the relay closes to make contact for the 
GPI output. The red LED continues to be lit 
until the temperature has cooled down below 
118.6
°
F (48
°
C), when the relay resets itself 
and the GPI output.
Under-Voltage Sensing 
(green)
The green LED indicates that the buck 
converter is regulating correctly, (that is 9.5 V 
to 10 V are established across the fans). If the 
voltage across the fans falls below 8.8 V, the 
green LED turns off, the red LED turns on, 
and the relay closes the contact for the GPI 
output to indicate bad voltage regulation. The 
green LED should always be lit to indicate 
correct voltage across the fans.
Over-Voltage Protection 
(OVP) and Sensing (red)
This feature protects the power distribution 
circuitry from over-voltage conditions, 
starting at 15 V, up to a maximum of 19 V. If 
such a condition occurs, the power to the 
converter is removed, the red LED turns on, 
and the relay closes the contact for the GPI 
output.