Recommended Supply Ductwork Sizes 
Blower Size 
Duct Size 
Straight Duct Length 
10 
14 x 14 
48 in. 
12 
16 x 16 
54 in. 
15 
20 x 20 
72 in. 
18 
24 x 24 
86 in. 
20 
26 x 26 
108 in. 
25 
32 x 32 
168 in. 
through vertical portion of the ventilator base 
assembly flange using a minimum of eight (8) lug 
screws, anchor bolts, or other suitable fasteners (not 
furnished).  Shims may be required depending upon 
curb installation and roofing material.  Check all 
fasteners for tightness.  The diagrams below show 
different mechanical installation configurations.     
 
Adequate building relief shall be provided so as to 
not over pressurize the building when the heating 
system is operating at its rated capacity.  This can be accomplished by taking into account, through 
standard engineering methods, the structure’s designed infiltration rate; by providing properly sized relief 
openings; or by interlocking a powered exhaust system; or by a combination of these methods. 
 
Heaters installed with intake ductwork must be purged to replace at least four air changes of the volume 
of the intake duct. 
 
If the failure or malfunction of this heater creates a hazard to other fuel burning equipment in the building 
(e.g. when the heater is providing make up air to a boiler room), the unit is to be interlocked to open inlet 
air dampers or other such devices. 
 
Units being installed in airplane hangars should be installed in accordance with the Standard for Aircraft 
Hangars, ANSI/NFPA 409.  Units being installed in public garages should be installed in accordance 
with the Standard for Parking Structures, ANSI/NFPA 88A, or the Standard for Repair Garages, 
ANSI/NFPA 88B, and with CAN/CGA B149 Installation Codes. 
Roof Mount Installation 
 
Installation with Exhaust Fan