Energy Tech Laboratories MR212 Manuale Utente

Pagina di 28
 
8
Gas Pressure Table 
Gas Pressure Type 
Gas Pressure 
Size 1-3 Inlet Pressure 
7 in. w.c. – 14 in. w.c. 
Size 4-5 Inlet Pressure 
7 in. w.c. – 5 psi. 
Max. Manifold Pressure - Natural Gas 
5 in. w.c. maximum 
Max. Manifold Pressure - Propane 
2.5 in. w.c. maximum 
Gas Connection Sizes 
Unit Size 
Gas Pipe Size (NPT) 
Size 1 
¾” 
Size 2 
1” 
Size 3 
1” 
Size 4 
1-1/4” 
Size 5 
1-1/2” 
Gas Connection Diagram 
Gas 
Installation of gas piping must conform with local building codes, or in the absence of local codes, with the 
National Fuel Gas Code, ANSI Z223.1 (NFPA 54) – latest edition.  In Canada, installation must be in 
accordance with CAN/CGA-B149.1 for natural gas units and CAN/CGA-B149.2 for propane units. 
WARNING: INLET GAS PRESSURE MUST NOT EXCEED PRESSURE INDICATED 
ON NAMEPLATE.  SEE UNIT NAMEPLATE FOR PROPER GAS SUPPLY 
PRESSURE AND GAS TYPE. 
1. Always disconnect power before working on or near a heater.  Lock and tag the disconnect 
switch or breaker to prevent accidental power up. 
2.  Piping to the unit should conform with local and national requirements for type and volume of gas 
handled, and pressure drop allowed in the line.  Refer to the Gas Engineer’s Handbook for gas 
line capacities. 
3.  The incoming pipe near the heater should be sized to 
match the connection on the outside of the unit. Unit inlet 
sizes are shown in the table to the right.  Avoid multiple 
taps in the gas supply so the unit has a steady supply of 
gas at all times. 
4.  Install a ground joint union with brass seat and a manual 
shut-off valve external to the unit casing, as shown below, 
adjacent to the unit for emergency shut-off and easy 
servicing of controls. 
5.  Provide a sediment trap, as shown below, before each 
unit and where low spots in the pipe line cannot be avoided.   
6.  Blow out the gas line to remove debris before making connections.  Purge line to remove air 
before attempting to start unit.  Purging of air from gas lines should be performed as described in 
ANSI Z223.1-latest edition “National Fuel Gas Code”, or in Canada in CAN/CGA-B149. 
7.  All field gas piping must be pressure/leak tested prior to unit operation.  Use a non-corrosive 
bubble forming solution or equivalent 
for leak testing.  The heater and its 
individual shut-off valve must be 
disconnected from the gas supply 
piping system during any pressure 
testing of that system at test 
pressures in excess of ½ psi.  The 
heater must be isolated from the gas 
supply piping system by closing its 
individual manual shutoff valve 
during any pressure testing of the gas supply piping system at test pressures equal to or less 
than ½ psi. 
8.  This unit requires a constant 7 in. w.c. minimum 
natural gas supply, when the unit is operating at 
maximum gas flow.  If the gas supply exceeds 14 in. 
w.c.
 (5 psi. for sizes 4-5 housings) it will damage the 
internal valve components, and if it is below 7 in. 
w.c., the heater may not perform to specifications. 
 
 
 
NOTICE
 
Refer to the heater rating 
plate for determining the 
minimum gas supply 
pressure for obtaining the 
maximum gas capacity for 
which this heater is specified.