TROUBLE 
POSSIBLE  CAUSE 
REMEDY 
REFRIGERATION  SYSTEM
 
No  electric  power  to  outlet. 
Turn  on  electric  power  outlet. 
The  thermostat  is  misadjusted  or 
defective. 
Adjust  or  replace  the  thermostat,  as 
necessary. 
The  wires  leading  to  the  thermostat  are 
defective  or  are  not  connected. 
Check  the  internal  wiring. 
Make  repairs  as  necessary. 
The  line  voltage  is  low. 
Check  the  line  voltage.  It  must  be  at 
least  90%  of  minimum  voltage. 
The  compressor  over-load 
Protector  (OLP)  is  defective. 
Replace  the  defective  over-load 
protector. 
The  starting  relay  (PTC)  is  defective. 
Replace  the  starting  relay. 
A.  Compressor  does 
not  run. 
The  compressor  is  defective. 
Replace  the  compressor. 
Return  cooler  to  authorized  service 
center  or  factory  for  repair. 
Poor  ventilation. 
Minimum  side  &  rear  clearance  4" 
The  condenser  is  dirty  or  restricted. 
Clean  the  condenser  or  relocate  the 
unit  to  prevent  restricting  the 
condenser. 
The  thermostat  is  defective.  (the 
contacts  are  shorted  or  the  control  is 
not  adjusted  properly) 
Replace  or  adjust  the  thermostat  as 
necessary. 
B.  Water  is 
adequately  chilled, 
but  cooler  runs 
excessively  or 
continuously. 
The  ambient  temperature  is  high. 
It  is  normal  for  the  cooler  to  run 
continuously  at  high  ambient 
temperatures. 
There  has  been  a  substantial  loss  in 
the  sealed  system's  charge  of 
refrigerant. 
If  refrigerant  leak  is  suspected,  return 
cooler  to  authorized  service  center  or 
factory  for  repair. 
C.  The  cooler 
compressor  runs 
continuously,  but  I 
do  not  have  cold 
water. 
The  compressor  is  defective. 
Same  as  above. 
The condenser is dirty or restricted. 
Clean the condenser and relocate the 
cooler to prevent restricting the condenser. 
The cold water thermostat is set high and 
or the cooler is in a high ambient 
environment. 
Check the thermostat setting. 
Adjust the setting as necessary. 
Usage of the cold water system is greater 
than the cooler capacity. 
Inform the customer of the cold water 
system's maximum capacity. 
The temperature of supply water is too high  Wait for a moment until cold water is made 
The refrigeration system is overcharged or 
undercharged. 
D. The cooler 
excessively 
and the cold water is 
not 
cold  enough. 
There is a partial restriction in the 
refrigeration system. 
Return cooler to authorized service center 
or factory for repair. 
E. The cooler has a 
If wattage readings are normal, the 
Replace the thermostat.