1.7.  Specifications 
Category 
HGM-SZ Specifications 
Product Type 
Single-zone infrared  monitoring system for low level continuous monitoring of CFC, HCFC 
and HFC refrigerant gasses used in most commercial refrigeration systems. System design 
supports compliance to the refrigerant monitoring requirements of ANSI/BSR ASHRAE 15-
2007 and ASHRAE Safety Code 34-2007. 
Gas Library: 
 
 
CFC 
HFP, R-11, R-113, R-114, R-12, R-502 
 
HFC 
R-125, R-134a, R-236FA, R-245Fa, R-404a (HP62), R-407a, R-407c (AC9000), R-410a 
(AZ20), R-422a, R-422d, R-427a, R-507 (AZ50), R-508b (SUVA95) 
 
HCFC 
R-123, R-124, R-21, R-22, R-227, R-23, R-401a (MP39), R-402a (HP80), R-402b (HP81), 
R-408a, R-409a, R-500, R-503 
 
HALON 
H1211, H1301, H2402 
 
Other 
FA188, FC72, HFO1234YF, N1230, R-420a, R-424a, R-426a, R-427a, R-438a 
Sensitivity 
All gasses 1 ppm 
Measuring 
Range
 
All gasses 0 to 10,000 ppm 
Accuracy 
±1 ppm ±10% of reading from 0-1000 ppm 
(R11, R22, R113: ±10 ppm ±15% of reading 0-1000 ppm) 
Response Time 
105 seconds maximum (dependent on sample line length) 
 
 
Category 
AGM-SZ Specifications 
Product Type 
Single zone infrared monitoring system for low level continuous monitoring of ammonia 
refrigerant gas used in most commercial refrigeration systems. 
Gas Library 
Ammonia / NH
3
 / R-717 
Sensitivity 
20 PPM (minimum detection limit) 
Measuring Range 
25-10,000 PPM 
Accuracy 
±10 ppm ±10% of reading from 25 to 1,000 ppm 
Response Time 
180 seconds maximum (dependent on sample line length)