Burnham MPC (Multi-Pass Commercial) Istruzione Sull'Installazione

Pagina di 108
3
This boiler has a limited warranty, a copy of which is printed on the back of this manual.
It is the responsibility of the installing contractor to see that all controls are correctly installed and are 
operating properly when the installation is complete.  The warranty for this boiler is valid only if the boiler 
has been installed, maintained and operated in accordance with these instructions.
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal 
injury or loss of life.  Failure to follow all instructions in the proper order can cause personal injury or 
death.  Read and understand all instructions, including all those contained in component manufacturers 
manuals which are provided with the appliance before installing, starting-up, operating, maintaining or 
servicing this appliance.  Keep this manual and literature in legible condition and posted near appliance 
for reference by owner and service technician.
This boiler requires regular maintenance and service to operate safely.  Follow the instructions contained 
in this manual.  
Installation, maintenance, and service must be performed only by an experienced, skilled and knowledgeable 
installer or service agency.     
All heating systems should be designed by competent contractors and only persons knowledgeable in 
the layout and installation of hydronic heating systems should attempt installation of any boiler.
It is the responsibility of the installing contractor to see that all controls are correctly installed and are 
operating properly when the installation is completed.
Installation is not complete unless a pressure relief valve is installed into the specified tapping on the 
supply manifold located on top and at rear of appliance - See Section III, Paragraph R, Item 3 of this 
manual for details.
This boiler is NOT suitable for installation on combustible flooring. 
Do not tamper with or alter the boiler or controls.  Retain your contractor or a competent serviceman to 
assure that the unit is properly  adjusted and maintained.
Clean boiler at least once a year - preferably at the start of the heating season to remove soot and scale.  
The inside of the combustion chamber should also be cleaned and inspected at the same time.
Have Burner and Controls checked at least once a year or as may be necessitated.  Do not operate 
unit with jumpered or absent controls or safety devices.  Do not operate unit if any control, switch, 
component, or device has been subject to water.
This boiler is designed to operate with lower return water temperatures and avoid thermal shock and 
accumulation of condensate if operated per the following criteria: 
     •   Minimum Return Water Temperature = 80°F
     •   Maximum Delta T Between Boiler Supply and Return = 80°F
     •   Minimum Supply Water Temperature = 130°F
Continued operation beyond these limitations will result in sustained condensing within the combustion 
chamber and potentially reduce boiler longevity and may result in premature boiler failure through 
thermal shock.
DO NOT store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other 
appliance.
If you smell gas or fuel oil vapors, do not try to operate the burner/boiler system.  Do not touch any 
electrical switch or use any phone in the building.  Immediately call the gas or oil supplier from a remotely 
located phone.
Burner/boiler systems produce steam or hot water in a pressurized vessel by mixing extremely flammable 
gaseous, liquid or solid fuels with air to produce combustion and very hot products of combustion.  
Explosions, fires severe personal injury, death and/or property damage will result from improper, careless 
or inadequate installation, operation or maintenance of fuel-burning and boiler equipment.