Appendix D -DC Power 
 
The DC power version of the ConsoleServer 800 must be installed in a restricted access 
location
.  Per the intent of the National Electrical Code, a restricted access location is an 
area intended for access by qualified or trained personnel only, with access controlled by 
some sort of locking mechanism, such as a key lock or access card system. 
 
Installation: 
 
Materials: 
  small flat-blade screwdriver  
 wire 
stripper 
  ConsoleServer 800 DC power connector kit 
  wires to 48 VDC power (see Appendix D for specifications) 
 
1. 
Turn off the circuit breaker to the DC power supply. 
 
2. 
Select a three-wire set (-48V, –48 Return, and Power Supply Ground) from the 
power supply. 
 
3. 
Strip 0.35 inches (89 mm) of insulation from each wire. 
 
4. 
Insert a small flat-blade screwdriver in the provided connector to depress the 
internal wire clamp. 
 
5. 
Insert the appropriate wire into the connector.  Remove the screwdriver.  Check 
that the clamp has captured the wire.  Repeat steps 4 and 5 for all wires. 
 
6. 
Attach the provided strain relief to the connector.  Be sure to use a tie-wrap to 
firmly attach the strain relief to the cable. 
 
7. 
Attach the connector to the socket on the back of the ConsoleServer.  Repeat the 
above steps to attach the redundant power input. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
o
Fan 
Power On/Off Switch 
 
Feed Through Headers 
48V Return 
PSU Gnd 
-48V DC