VENTING INSTALLATION
Continued
Figure 9 - Elbow Offset
B
A
Screws
FIRESTOP SPACERS (FS-10, 
1100EFS-10DM FOR JM36)
Firestop spacers are required at each point where 
the chimney penetrates a floor space. Their purpose 
is to establish and maintain the required clearance 
between the chimney and the combustible materials. 
When the pipe passes through a framed opening into 
a living space above, the firestop must be placed onto 
the ceiling from below as shown in Figure 10.
They also provide complete separation from one floor 
space to another or attic space as required by most 
codes. When the double wall pipe passes through a 
framed opening into an attic space, the firestop must 
be placed into an attic floor as shown in Figure 11.
Figure 10 - Firestop Spacer with Living 
Space Above Ceiling
Figure 11 - Firestop Spacer with Attic 
Space Above Ceiling
Existing 
Ceiling 
Frame
Firestop 
Spacer
Screws or 
Staples 
(Min. of 8)
Firestop 
Spacer
Screws or Staples 
(Min. of 8)
PENETRATING THE ROOF
To maintain a 1" (JM36) or 2" (JM42/JM50) clear-
ance to the pipe on a roof with a pitch, a rectangular 
opening must be cut.
1.  Determine the center point through which the 
pipe will penetrate the roof.
2.  Determine the center point of the roof. Pitch 
is the distance the roof drops over a given 
span, usually 12". A 6/12 pitch means that 
the roof drops 6" for each 12" one measure 
horizontally down from the roof rafters.
3.  Use  the  roof  opening  chart  (Figure  12)  to 
determine  the  correct  opening  length  and 
flashing required.
17" Min.
(432mm)
30" Min.
(762mm)
1" Min.
(25mm)
1" Min.
(25mm)
1" Min.
(25mm)
Opening "A"
Roof Opening JM36
Pitch
Slope
Opening "A" 
Max. 
Used Flashing
Model No. 
Flat
17"
V6F-10DM
0-
6/12
26.6°
19"
V6F-10DM
6/12-
12/12
45.0°
24"
V12F-10DM
Roof Opening JM42/50
Pitch
Slope
Opening "A" 
Max.
Used Flashing
Model No. 
Flat
19.5"
V6F-10DM
0-
6/12
26.6°
22'
V6F-10DM
6/12-
12/12
45.0°
27"
V12F-10DM
Existing 
Ceiling 
Frame
19.5" Min.
(495mm)
30" Min.
(762mm)
2" Min.
(51mm)
2" Min.
(51mm)
2" Min.
(51mm)
Opening "A"
Figure 12 - Roof Opening Measurements