FiReplace inStallatiOn
SELECTING LOCATION
To determine the safest and most efficient location 
for the fireplace, you must take into consideration 
the following guidelines:
1.  The location must allow for proper clearances 
(see Figures 1 and 2).
2.  Consider a location where the fireplace will 
not be affected by drafts, air conditioning 
ducts, windows or doors.
3.  A location that avoids the cutting of joists or 
roof rafters will make installation easier.
4.  An outside air kit is available with this fireplace 
(see Optional Outside Air Kit on page 8).
MINIMUM CLEARANCE TO 
COMBUSTIBLES
Back and sides of fireplace   3/4" minimum*
Floor** 
0" minimum
Perpendicular wall to opening  12" minimum
Top spacers 
0" minimum
Mantel clearances 
see Mantels, page 5
Chimney outer pipe surface  1" minimum
* Not required at nailing flanges
** See step 2 of Framing
 WARNING: Do not pack re-
quired air spaces with insulation 
or other materials.
Minimum/Maximum Chimney Height for 
Residential Installation
The minimum height of the chimney, measured 
from the base of the fireplace to the flue gas outlet 
of the termination, is 14.5 feet for straight flue or 
a flue with one elbow set. The maximum distance 
between elbows is 6 feet. For systems with two 
elbow sets, the minimum height is 22 feet. The 
maximum height of any system is 50 feet. This 
measurement includes the fireplace, chimney sec-
tions and the height of the termination assembly 
at the level of the flue gas outlet (see Figure 18, 
page 11).
Minimum/Maximum Chimney Height for 
Outdoor Installation
The minimum height of the chimney, measured 
from the base of the fireplace to the flue gas outlet 
of the termination, is 7 
1
/
2
 feet (minimum of 4 feet 
of chimney pipe sections required for outdoor 
installation).
FRAMING
1.  Frame the opening for the fireplace using the 
dimensions shown in Figures 1 and 2.
2.  If the fireplace is to be installed directly on 
carpeting, tile (other than ceramic) or any 
combustible material other than wood floor-
ing, the fireplace must be installed upon a 
metal or wood panel extending the full width 
and depth of the fireplace.
3.  Set the fireplace directly in front of this open-
ing and slide the unit back until the nailing 
flanges touch the side framing.
4.  Check the level of the fireplace and shim with 
sheet metal if necessary.
5.  Before securing fireplace to prepared fram-
ing,  the  ember  protector  (provided)  must 
be placed between the hearth extension (not 
supplied) and under the bottom front edge 
of the fireplace to protect against glowing 
embers falling through. If the fireplace is to be 
installed on a raised platform, a Z-type ember 
protector (not supplied) must be fabricated to 
fit your required platform height. The ember 
protector should extend under the fireplace a 
minimum of 1 
1
/
2
". The ember protector should 
be made of galvanized sheet metal (28 gauge 
minimum) to prevent corrosion.
6.  Using screws or nails, secure the fireplace to 
the framing through flanges located on the 
sides of the fireplace.
21.875”
41.375”
41.250”
Figure 1 - Framing Dimensions
52.183"
17.253"
24.399"
73.798"
MAINTAIN 
3
/
4
"
CLEARANCE AT
SIDES AND BACK
OF FIREPLACE
3
/
4
" CLEARANCE
NOT REQUIRED AT
NAILING FLANGES  
Figure 2 - Corner Installation