Toshiba 4200FA XT1 Manuale Utente

Pagina di 10
 
4200FA XT1  
 
 
September 6, 2004
 
 
2
(50 kVA XT) 
 
1.0 SCOPE 
 
 1.1 
System 
 
This specification describes a continuous duty, three-phase, on-line, solid-
state uninterruptible power supply system, hereafter referred to as the 
UPS. 
 
2.0 SYSTEM DESCRIPTION 
 
2.1 Applicable 
Standards 
 
The UPS shall be designed in accordance with and be compliant with the 
following sections of the current revisions of the following standards: 
 
 
ANSI C62.41 (IEEE 587) – Standard for Surge Withstandability 
 
UL 1778 (CUL) 
 
National Electrical Code (NFPA-70) 
 NEMA 
PE-1 
 OSHA 
 ASME 
 
ISO 9001, 14001 
 
 2.2 
Components 
 
The UPS shall consist of the following components: 
 
A. Converter 
 
B. Chopper / Charger 
 
C. Pulse-Width Modulated (PWM) Inverter 
 
D. Static Switch Bypass 
 
E. Microprocessor Controlled Logic and Control Panel 
 
F. Input Circuit Breaker 
 
G. Battery System