GE AF-300 Manuale Utente

Pagina di 98
 
Change during operation: N = impossible, Y* = possible (enabled by using             ), Y= possible (enabled by using 
 
 ) 
 
 
-36- 
FUNC 
DATA
 
 
 
Func-
tion 
code 
No.
 
Name
 
Setting range
 
Unit
 
Min. 
unit
 
Factory 
setting
 
Change 
during 
operation
 
User 
setting 
P00 
Motor characteristics
 
0 to 10 
-
 
-
 
 
 
 
 
Func-
tion 
code 
No.
 
Name
 
Setting range
 
Unit
 
Min. 
unit
 
Factory 
setting
 
Change 
during 
operation
 
User 
setting 
H01 
Operation time
 
Operation time accumulation
 
100Hr
 
-
 
 
H02 
Trip history
 
The contents of the last four alarms are 
displayed sequentially.
 
-
 
-
 
---
 
-
 
 
H03 
Data initialization
 
1: Initialized  
(return to factory setting value)
 
-
 
-
 
N
 
 
H04 
Auto-reset
 
0: Inactive 
 
1: Active (5 times fixed)
 
-
 
-
 
Y* 
 
H06 
Fan Stop Operation
 
0: Inactive
 
1: Active
 
-
 
-
 
Y* 
 
H20 
PID control
   
      (
Mode select)
 
0: Inactive
 
1: Active (Normal operation)
     
2: Active (Inverse operation)
 
-
 
-
 
N
 
 
H21 
(Feedback signal)
 
0:
Terminal 
[12] 
             (0 to +10Vdc) 
Input
 
1:
Terminal 
[C1] 
             (4 to 20mAdc)
Input
 
2:
Terminal [
12] 
             (+1 to +5Vdc) 
Input
 
-
 
-
 
N
 
 
H22 
(
P-gain
0.01 to 10.0 times (1to1000%)
 
-
 
0.01 
0.01 
 
H23 
(
I-gain)
 
0.0s : 
Inactive
 
0.1 to 999s 
0.1 
0.0 
 
H24 
(D-gain)
 
0.00s : 
Inactive
 
0.01 to 10.0s 
0.01 
0.00 
 
H25 
(
Feedback filter)
 
0.0 to 60.0s 
0.1 
0.5 
 
H:  High Performance Functions  
P:  Motor Parameters