GE AF-300 Manuale Utente

Pagina di 98
 
Change during operation: N = impossible, Y* = possible (enabled by using             ), Y= possible (enabled by using 
 
 ) 
 
 
-37- 
FUNC 
DATA
 
 
 
Function 
code No. 
Name 
Setting range 
Unit 
Min. 
unit 
Factory 
setting 
Change 
during 
operation 
User 
setting 
o00 
RTU Option  
0 : Inactive 1 : Active 
Y* 
 
o01 
Address  
1 to 247 (Max – 31 Drives) 
 
 
Y* 
 
o02 
Mode select on no response 
error  
0   :          Er8 by 8 times communiction/checksum 
errors  
1   :          Er8 by 8 times communiction/checksum 
errors 
2   :          Er8 with no communication more than 
timer (o03) 
3   :          Retry and keep running 
 
 
 
Y* 
 
o03 
Timer  
1  to  60 s  
Y* 
 
o04 
Baud rate  
1 : 9600                2 : 4800  
 
3: 2400 
 - 
 
Y* 
 
o05 
Data length  
0 : 8 bits  (Fixed)  
 
Y* 
 
o06 
Parity check  
0 : No checking  
1 : Even parity,        2 : Odd parity  
 
Y* 
 
o07 
Stop bits  
0 : 2bits               1 : 1bit  
              (Automatically changed by o06 setting)  
 
Y* 
 
o08 
No response error detection 
time  
0 : (No detection)  
1  to  60 s  
Y* 
 
o09 
Response interval  
0.00  to  1.00 s  
0.1 
0.01 
Y* 
 
o10 
RTU Frequency Command   0 : F01 setting is active  
1 : RTU setting is active  
 
 
o11 
RTU Operation Command   0 : F02 setting is active  
1 : RTU setting is active  
 
 
Note: 
For details on “o01” to “o11”, refer to the instruction manual that came with the optional RS485 RTU 
serial communication option. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
O: Optional Functions