11.5     Join the Battery Cabinet with the UPS 
The Toshiba Battery Cabinet (431B) is equipped with four 14 mm mating holes located on the front and 
back of the left and right sides of the cabinet. 
1.  Ensure Battery Cabinet Breaker are OFF.
WARNING
Switch the Battery Cabinet Circuit Breakers off before removing dead fronts.
Failure to switch breakers off  may result in electric shock, burns, personal injuries or 
UPS failure.
2.  Remove the UPS dead-fronts.
3.  Remove the cable access plate at the lower-front right side of the UPS Cabinet.
4.  Remove the cable access plate at the lower-front left side of the 431B Cabinet. (See Figure 11-4) 
5.  Position the 431B cabinet to the right of  and adjacent to the UPS Cabinet.
6.  Align the four 14 mm bolt holes on the left side of the 431B Cabinet with the matching four 14 mm bolt 
holes on the right side of the UPS Cabinet.  
7.  Bolt the cabinets together with four 3/8-16 in. x 2 in. long bolts.
Figure 11-4 - 431B Cable
 
    Access Plate